Installing fire doorsets correctly is essential for safety, compliance, and the performance of the door in a fire. Here’s a guide highlighting the main things to consider on site.

  1. Prepare the Opening

What to check:

  • Ensure the wall, ceiling and floor opening is square, level and true.
  • Complete first-fix wet trades first (plaster, screed) to avoid doorset distortion.
  • Know the floor finish thickness to set the correct threshold gap.

Why it matters: A well-prepared opening ensures the doorset fits properly without adjustments that could affect compliance.

 

  1. Priming & Sealing

What to do:

  • Prime or seal all exposed edges, top/bottom, and hardware apertures. Avoid damage or removal of the fire door certification label at the top of the door.
  • Follow paint or stain manufacturer guidance.

Why it matters: Proper sealing prevents warping and ensures the doorset maintains fire performance.

 

  1. Hardware Considerations

What to check:

  • Confirm hinges, closers, locks, and latches are compliant for the doorset.
  • Fit relevant compliant mortised hardware and any intumescent protection before hanging and installing the doorset. This can stop any damage to the doorset after installation. We also offer a full ironmongery solution as part of our Architectural range.
  • Lubricate moving parts as recommended.

Why it matters: Correctly installed and regularly maintained hardware ensures the doorset will operate correcty and will comply with fire certification throughout its life cycle.

 

  1. Hanging the Fire Doorset

What to do:

  • Use compliant packers to keep the frame square and plumb.
  • Fixings should penetrate at least 50mm into the wall
  • Maintain the correct operating gaps around the door in line with the fire door manufacturer’s instructions:

Side and Head Gaps: 2–4 mm (ideally 3 mm).

Bottom Threshold Gap:

Fire only – 8mm as standard but this will vary so you must check the relevant fire door manufacturer’s certificate report for the door to achieve compliance.

Fire & additional smoke control without using a compliant automatic drop seal is a maximum 3mm.

Fire & additional smoke control using a compliant automatic drop seal is the same as the fire door manufacturer’s certification for ‘fire only’.

  • Fire doors have traceability and certification info on the top edge – never remove or cover it.
  • Doorset frames and  door leaves should not be trimmed or adjusted without the manufacturer’s prior permission. Any minor adjustments should only be done once the doorset has been conditioned in a dry and stable environment.

Why it matters: Correct gaps ensure the doorset closes properly, seals effectively, and meets fire certification standards.

 

  1. Seals & Thresholds

What to check:

  • Ensure the correct specified and compliant seals are installed correctly to the manufacturer’s guidance. MBP offer options of pre-fitted or supplied loose for site installation.
  • Compression seals should be around 50% compressed; blade/brush seals should overlap 1–1.5mm.
  • Adjust threshold gaps according to flooring and certification requirements.

Why it matters: Correctly specified and compliant seals and thresholds prevent smoke or fire from bypassing the doorset, maintaining its protective performance.

 

  1. Finishing Touches

What to do:

  • Fit door stops after all adjustments, decoration and any retro-seal installation to ensure the door leaf face is flush to the door frame.
  • Use certified fire stopping sealant to seal the gaps behind the frame and architraves.
  • Conceal fixings for a neat finish and record the installation procedure as required.

Why it matters: Ensures the doorset remains compliant, functions correctly, and looks professional.

 

Proper installation of fire doorsets saves lives, ensures compliance, and avoids costly remedial work. Focus on prepared openings, correct gaps, certified seals, and careful hardware fitting.

Always follow the manufacturer’s installation guidance to ensure your doorset is installed correctly, is compliant and will perform in the event of a fire.

Download the MBP Doorset Installation Guide for more detailed information.

MBP Door Solutions offers customised fire and acoustic doorsets tailored to residential, commercial, education and leisure environments.

Download our latest catalogue.

Contact us to find out more.